冷庫組件蒸發器的安裝規范
The installation of cold storage components evaporator specification
安裝內容:先把吊裝螺絲孔開好,并開好銅管及電線孔,后二孔要修整以防快口留下隱患,自配排水管的蒸發器背面與立板定位為 300MM ,蒸發器排水孔與立板預先安好的排水孔位垂直,兩者間高差為 250MM 。
Install content: the lifting screw holes open first, open good copper pipe and wire hole, and after two hole to repair in case of quick mouth left hidden trouble, since with a drain on the back of the evaporator and vertical plate positioning is 300 mm, the evaporator drain and vertical plate be just fine a vertical drain holes in advance, elevation difference between is 250 mm.
如是冷凍庫,排水管內穿排水電熱絲,排水電熱絲發熱部位,只能伸到庫板內 50MM 處,排水管外部保溫處理,冷藏不需電熱絲,其它相同。
食品冷庫
Heating wire, the freezer, the drainage tube wear drainage, drainage heating wire heating parts, can only be stretched to the base plate within 50 mm, drainage pipe external heat preservation processing, cold storage without heating wire, the other is the same.
吊裝注意:蒸發器進風口不能對著庫門,蒸發器最好吊放在冷庫最長端,蒸發器出風口最好不要對著門,(蒸發器取位居中,以便維修)。
Hoisting note: evaporator air inlet can't to the door, evaporator best hanging on the side, the longest refrigerator evaporator outlet had better not to the door, (evaporator in the, in order to repair).